Data loggers
MPI-D
Data logger with 2GB internal flash memory in panel case. The recorder is intended to measure process values in industrial applications. It is designed to work with devices and sensors that communicates by digital bus: RS-485 standard with Modbus RTU protocol and HART standard (also in multidrop configuration).
Multi-channel data logger in panel case
• 20 measuring channels
• Interaction with RS-485 / Modbus RTU transducers and devices and HART devices (also in multidrop mode)
• 2 binary inputs
• 16 calculation channels
• 4 relay outputs – alarm and control functions
• Internal 2GB data memory, advanced data recording
• Color graphic LCD TFT display
• USB port on front panel with IP54 protection
• Ethernet port (Modbus TCP protocol, server www)
• RS-485 port (Modbus RTU protocol)
• Dedicated software for visualization of measurement results
Measurment channels
• 18 channels intended for reading transducers or other devices operating in the Modbus RTU standard and HART protocol transducers
• 2 channels intended for interaction with PULS-type inputs (measurement of frequencies within the range of 0.001Hz … 10kHz, pulse counting, tracking and recording the shorting / disconnecting binary signal)
HART
• Readout of digital quantities from transducers / devices connected in parallel to a current loop
• Operation as Primary Master or Secondary Master
• Readout of variables: PV – primary variable, SV – secondary variable, TV – third variable, FV – fourth variable
MODBUS RTU
• Devices / transducers connected in parallel to one pair of wires (of an RS-485(1) port)
• Transmission rate between 1200bps and 115,200bps
• Readout functions: 03 (Read Holding Register) and 04 (Read Input Register)
• Supported formats of variables: Uns. Integer, Integer, Uns. Long, Uns. Long(sw), Long, Long(sw), Float, Float(sw)
16 Calculated values
• Available functions: addition, subtraction, multiplication, division and extraction of roots
Recording measurement results
• Recording to internal 2GB memory
• Checksum secured files – protection against result errors
• Recording frequency between 3 s and 24 h; define two recording frequencies toggled upon exceeding the set alarm thresholds
4 relay outputs, alarm and control thresholds
• 4 semiconducting output relays rated at 0.1A / 60V
• Up to 4 alarm thresholds for each input and each calculated value
Other functions
• Totalizers – two totalizers per flow value (measured or calculated)
• Tracking minimum, maximum and average values
• Advanced user and password system
• Event Log
• Authorized Operations Log
• Available also in wall-mounted case – MPI-DN
Application
The MPI-D, MPI-DN recorders are used in the energy, chemical, pharmaceutical, food, metallurgical industries, manufacturing, laboratories, and wherever it is necessary to register digital measurement. Example of application: monitoring of compressed air and gas flow parameters.
This product is CE marked.
Declarations of Conformity are available on request.
FRONT PANEL | ||
Display type | LCD TFT colour 272×480 px | |
Display size | 43.8 mm x 77.4 mm | |
Keyboard | · MPI-D: 7 membrane buttons
· MPI-DN: 19 membrane buttons |
|
LED indication | 3 LEDs 3-colour, red-orange-green | |
INPUTS ORGANIZATION | ||
MPI-D, MPI-DN |
Port HART: Port RS-485 (1): 2 x PULS: IN19, IN20 |
|
RS-485 (1) serial port – Master | ||
Transmission protocol | Modbus RTU | |
Data format | Uns. Integer, Integer, Uns. Long, Uns. Long (sw), Long, Long (sw), Float, Float (sw) | |
Frequency of reading | 3 s, 4 s, 5 s, 6 s, 10 s, 12 s, 15 s, 30 s, 1 min | |
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbps | |
Address space of transducers | 1 .. 247 | |
Maximum load | 32 receivers/transmitters | |
Maximum line length | 1200 m | |
Maximum differential voltage A(+) – B(-) | -7 .. +12 V | |
Maximum total voltage A(+) – ‘ground’ or B(-) – ‘ground’ |
-7 .. +12 V | |
Minimal output signal from transmitter | 1.5 V (for R0 = 54 Ω) | |
Minimum receiver sensitivity | 200 mV / RIN = 12 kΩ | |
Minimum impedance of data transmission line | 54 Ω | |
Internal terminating resistor | Yes, activated by short-circuit pins on terminal block | |
Short-circuit/thermal protection | Yes/Yes | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
HART port | ||
Transmission protocol | Master type 0 or 1, rev. 4, rev. 5, rev. 6; FSK | |
Implemented features | Reading variables PV, SV, TV, FV
Retrieve long address (rev. 5, rev. 6) Change of short address |
|
Multidrop mode | Yes, up to 12 devices | |
Loop power | 24 VDC (max 50 mA) | |
Analog line 4-20mA reading | No | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
PULS type inputs (binary/pulse/frequency) | ||
Number of inputs | 2 | |
Maximum input voltage | ±28 VDC | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
Functions | State detection
Pulse counting Frequency measurement |
|
Measuring range | 0.001 Hz .. 10 kHz
(0.001 Hz .. 1 kHz with filtrating capacitor) |
|
Minimum impulse width | 20 ms
0.5 ms with filtrating capacitor |
|
Accuracy (at Ta = +20 °C) | 0.02% | |
Configuration: OC/contact(1) | ||
Open circuit voltage | 12 V | |
Short circuit current | 12 mA | |
On/off threshold | 2.7 V / 2.4 V | |
(1)The default setting. | ||
Configuration: voltage input | ||
Input resistance | 1 kW | |
On/off threshold | 2.7 V / 2.4 V | |
Open circuit voltage | 12 V | |
Configuration: Namur | ||
High impedance state | 0.4 .. 1 mA | |
Low impedance state | 2.2 .. 6.5 mA | |
Binary outputs (Solid State Relays) | ||
Number of outputs | 4 | |
Type of outputs | Solid State Relays | |
Maximum load current | 100 mA DC/AC | |
Maximum voltage | 60 V DC/AC | |
Galvanic isolation between outputs | 400 VAC (functional isolation) | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
4-20mA analogue output (optional) | ||
Number of outputs | 1 | |
Output signal | 4-20mA (3.6–22 mA) | |
Maximum voltage between I+ and I- | 28 VDC | |
Loop resistance (at Ucc = 24 V) | 0 .. 500 Ω | |
Converter resolution D/A | 16 bit | |
Accuracy | 0.5% | |
Current loop supply | External or internal power supply 24 VDC / 22 mA | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
RS-485 (2) serial port – Slave | ||
Maximum load | 32 receivers/transmitters | |
Maximum line length | 1200 m | |
Maximum differential voltage A(+) – B(-) | -7 .. +12 V | |
Maximum total voltage A(+) – ‘ground’ or B(-) – ‘ground’ |
-7 .. +12 V | |
Minimal output signal from transmitter | 1.5 V (for R0 = 54 W) | |
Minimum receiver sensitivity | 200 mV / RIN = 12 kW | |
Minimum impedance of data transmission line | 54 W | |
Internal terminating resistor | Yes, activated by short-circuit pins on terminal block | |
Short-circuit/thermal protection | Yes/Yes | |
Transmission protocol | ASCII
Modbus RTU |
|
Baud rate | 2.4, 4.8, 9.6 ,19.2, 38.4, 57.6, 115.2 kbps | |
Parity control | Even, Odd, None | |
Frame | 1 start bit, 8 data bits, 1 stop bit | |
Galvanic isolation | No | |
Ethernet port | ||
Transmission protocol | Modbus TCP, ICMP (ping), DHCP server, http server | |
Interface | 10BaseT Ethernet | |
Data buffer | 300 B | |
Number of opened connections (simultaneously) | 4 | |
Connector type | RJ-45 | |
LED signaling | 2, build in RJ-45 socked | |
USB port | ||
Socket type | A type, according to USB standard | |
Version | USB 1.1 | |
Socket protection class | IP54 | |
Recording format | FAT16 (within a limited scope) | |
Recording indication | red-orange-green LED on the front panel | |
Internal data memory | ||
Capacity | 2 GB | |
Estimated recording time for recording speed every 3 s for 16 measuring channels | ca. 400 days | |
MPI-D power supply | ||
Supply voltage | 24 VAC (+5%/-10%) or 24 VDC (15 .. 30 VDC) | |
Maximum power consumption | 5 VA / 5 W | |
MPI-DN power supply | ||
Supply voltage | 100 .. 240 VAC 50/60 Hz
or 24 VAC (+5%/-10%) or 24 VDC (15 .. 30 VDC) |
|
Maximum power consumption | 14 VA / 14 W (for 100 .. 240 VAC power supply)
5 VA / 5 W (for 24 VAC/VDC power supply) |
|
Wire terminals | ||
Type | · MPI-D: screw type terminal blocks
· MPI-DN: spring type terminal block |
|
Conductor cross section | · MPI-D: solid max. 1.5 mm2
· MPI-DN: stranded 0.2 .. 1.5 mm2 |
|
MPI-D enclosure – dimensions | ||
Enclosure type | Panel mount, nonflammable plastic material ‘Noryl’ | |
Dimensions (width x height x depth) | 144 mm x 72 mm x 130 mm | |
Enclosure depth with terminals | ca. 140 mm | |
Panel cut-out dimensions (width x height) | 138+1.0 mm X 68+0.7 mm | |
Panel maximum thickness | 5 mm | |
Weight | ca. 0.5 kg | |
Protection class from the front panel | IP54 | |
Protection class from the rear panel | IP30 | |
MPI-DN enclosure – dimensions | ||
Enclosure type | Wall mount, PC material | |
Dimensions (width x height x depth) | 257 mm X 217 mm X 125 mm (without cable glands)
257 mm X 247 mm X 125 mm (with cable glands) |
|
Weight | ca. 2.1 kg | |
Protection class | IP54 | |
Environmental conditions | ||
Ambient temperature | · MPI-D: 0 .. +50 °C
· MPI-DN: -20 .. +50 °C |
|
Relative humidity | 0 .. 75% (without steam condensation) | |
Storage temperature | -20 .. +80 °C | |
Overvoltage category | OV II | |
Pollution degree | PD 2 | |
LVD (safety) | EN 61010-1 | |
EMC | Directive 2014/30/EU:
· immunity for industrial environments according to EN 61326-1:2013 (Table 2) · conductive and radiated emissions Class A equipment according to EN 61326-1:2013 |
|
RoHS | Directive 2011/65/EU | |
Installation location | · MPI-D: Indoor only
· MPI-DN: Indoor or outdoor(2) |
|
(2)If additional protection against atmospheric precipitation is provided (roofing), the device can be installed outdoor. |
Multi-channel data logger in panel case
• 20 measuring channels
• Interaction with RS-485 / Modbus RTU transducers and devices and HART devices (also in multidrop mode)
• 2 binary inputs
• 16 calculation channels
• 4 relay outputs – alarm and control functions
• Internal 2GB data memory, advanced data recording
• Color graphic LCD TFT display
• USB port on front panel with IP54 protection
• Ethernet port (Modbus TCP protocol, server www)
• RS-485 port (Modbus RTU protocol)
• Dedicated software for visualization of measurement results
Measurment channels
• 18 channels intended for reading transducers or other devices operating in the Modbus RTU standard and HART protocol transducers
• 2 channels intended for interaction with PULS-type inputs (measurement of frequencies within the range of 0.001Hz … 10kHz, pulse counting, tracking and recording the shorting / disconnecting binary signal)
HART
• Readout of digital quantities from transducers / devices connected in parallel to a current loop
• Operation as Primary Master or Secondary Master
• Readout of variables: PV – primary variable, SV – secondary variable, TV – third variable, FV – fourth variable
MODBUS RTU
• Devices / transducers connected in parallel to one pair of wires (of an RS-485(1) port)
• Transmission rate between 1200bps and 115,200bps
• Readout functions: 03 (Read Holding Register) and 04 (Read Input Register)
• Supported formats of variables: Uns. Integer, Integer, Uns. Long, Uns. Long(sw), Long, Long(sw), Float, Float(sw)
16 Calculated values
• Available functions: addition, subtraction, multiplication, division and extraction of roots
Recording measurement results
• Recording to internal 2GB memory
• Checksum secured files – protection against result errors
• Recording frequency between 3 s and 24 h; define two recording frequencies toggled upon exceeding the set alarm thresholds
4 relay outputs, alarm and control thresholds
• 4 semiconducting output relays rated at 0.1A / 60V
• Up to 4 alarm thresholds for each input and each calculated value
Other functions
• Totalizers – two totalizers per flow value (measured or calculated)
• Tracking minimum, maximum and average values
• Advanced user and password system
• Event Log
• Authorized Operations Log
• Available also in wall-mounted case – MPI-DN
Application
The MPI-D, MPI-DN recorders are used in the energy, chemical, pharmaceutical, food, metallurgical industries, manufacturing, laboratories, and wherever it is necessary to register digital measurement. Example of application: monitoring of compressed air and gas flow parameters.
This product is CE marked.
Declarations of Conformity are available on request.
FRONT PANEL | ||
Display type | LCD TFT colour 272×480 px | |
Display size | 43.8 mm x 77.4 mm | |
Keyboard | · MPI-D: 7 membrane buttons
· MPI-DN: 19 membrane buttons |
|
LED indication | 3 LEDs 3-colour, red-orange-green | |
INPUTS ORGANIZATION | ||
MPI-D, MPI-DN |
Port HART: Port RS-485 (1): 2 x PULS: IN19, IN20 |
|
RS-485 (1) serial port – Master | ||
Transmission protocol | Modbus RTU | |
Data format | Uns. Integer, Integer, Uns. Long, Uns. Long (sw), Long, Long (sw), Float, Float (sw) | |
Frequency of reading | 3 s, 4 s, 5 s, 6 s, 10 s, 12 s, 15 s, 30 s, 1 min | |
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbps | |
Address space of transducers | 1 .. 247 | |
Maximum load | 32 receivers/transmitters | |
Maximum line length | 1200 m | |
Maximum differential voltage A(+) – B(-) | -7 .. +12 V | |
Maximum total voltage A(+) – ‘ground’ or B(-) – ‘ground’ |
-7 .. +12 V | |
Minimal output signal from transmitter | 1.5 V (for R0 = 54 Ω) | |
Minimum receiver sensitivity | 200 mV / RIN = 12 kΩ | |
Minimum impedance of data transmission line | 54 Ω | |
Internal terminating resistor | Yes, activated by short-circuit pins on terminal block | |
Short-circuit/thermal protection | Yes/Yes | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
HART port | ||
Transmission protocol | Master type 0 or 1, rev. 4, rev. 5, rev. 6; FSK | |
Implemented features | Reading variables PV, SV, TV, FV
Retrieve long address (rev. 5, rev. 6) Change of short address |
|
Multidrop mode | Yes, up to 12 devices | |
Loop power | 24 VDC (max 50 mA) | |
Analog line 4-20mA reading | No | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
PULS type inputs (binary/pulse/frequency) | ||
Number of inputs | 2 | |
Maximum input voltage | ±28 VDC | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
Functions | State detection
Pulse counting Frequency measurement |
|
Measuring range | 0.001 Hz .. 10 kHz
(0.001 Hz .. 1 kHz with filtrating capacitor) |
|
Minimum impulse width | 20 ms
0.5 ms with filtrating capacitor |
|
Accuracy (at Ta = +20 °C) | 0.02% | |
Configuration: OC/contact(1) | ||
Open circuit voltage | 12 V | |
Short circuit current | 12 mA | |
On/off threshold | 2.7 V / 2.4 V | |
(1)The default setting. | ||
Configuration: voltage input | ||
Input resistance | 1 kW | |
On/off threshold | 2.7 V / 2.4 V | |
Open circuit voltage | 12 V | |
Configuration: Namur | ||
High impedance state | 0.4 .. 1 mA | |
Low impedance state | 2.2 .. 6.5 mA | |
Binary outputs (Solid State Relays) | ||
Number of outputs | 4 | |
Type of outputs | Solid State Relays | |
Maximum load current | 100 mA DC/AC | |
Maximum voltage | 60 V DC/AC | |
Galvanic isolation between outputs | 400 VAC (functional isolation) | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
4-20mA analogue output (optional) | ||
Number of outputs | 1 | |
Output signal | 4-20mA (3.6–22 mA) | |
Maximum voltage between I+ and I- | 28 VDC | |
Loop resistance (at Ucc = 24 V) | 0 .. 500 Ω | |
Converter resolution D/A | 16 bit | |
Accuracy | 0.5% | |
Current loop supply | External or internal power supply 24 VDC / 22 mA | |
Galvanic isolation from supply voltage | 400 VAC (functional isolation) | |
RS-485 (2) serial port – Slave | ||
Maximum load | 32 receivers/transmitters | |
Maximum line length | 1200 m | |
Maximum differential voltage A(+) – B(-) | -7 .. +12 V | |
Maximum total voltage A(+) – ‘ground’ or B(-) – ‘ground’ |
-7 .. +12 V | |
Minimal output signal from transmitter | 1.5 V (for R0 = 54 W) | |
Minimum receiver sensitivity | 200 mV / RIN = 12 kW | |
Minimum impedance of data transmission line | 54 W | |
Internal terminating resistor | Yes, activated by short-circuit pins on terminal block | |
Short-circuit/thermal protection | Yes/Yes | |
Transmission protocol | ASCII
Modbus RTU |
|
Baud rate | 2.4, 4.8, 9.6 ,19.2, 38.4, 57.6, 115.2 kbps | |
Parity control | Even, Odd, None | |
Frame | 1 start bit, 8 data bits, 1 stop bit | |
Galvanic isolation | No | |
Ethernet port | ||
Transmission protocol | Modbus TCP, ICMP (ping), DHCP server, http server | |
Interface | 10BaseT Ethernet | |
Data buffer | 300 B | |
Number of opened connections (simultaneously) | 4 | |
Connector type | RJ-45 | |
LED signaling | 2, build in RJ-45 socked | |
USB port | ||
Socket type | A type, according to USB standard | |
Version | USB 1.1 | |
Socket protection class | IP54 | |
Recording format | FAT16 (within a limited scope) | |
Recording indication | red-orange-green LED on the front panel | |
Internal data memory | ||
Capacity | 2 GB | |
Estimated recording time for recording speed every 3 s for 16 measuring channels | ca. 400 days | |
MPI-D power supply | ||
Supply voltage | 24 VAC (+5%/-10%) or 24 VDC (15 .. 30 VDC) | |
Maximum power consumption | 5 VA / 5 W | |
MPI-DN power supply | ||
Supply voltage | 100 .. 240 VAC 50/60 Hz
or 24 VAC (+5%/-10%) or 24 VDC (15 .. 30 VDC) |
|
Maximum power consumption | 14 VA / 14 W (for 100 .. 240 VAC power supply)
5 VA / 5 W (for 24 VAC/VDC power supply) |
|
Wire terminals | ||
Type | · MPI-D: screw type terminal blocks
· MPI-DN: spring type terminal block |
|
Conductor cross section | · MPI-D: solid max. 1.5 mm2
· MPI-DN: stranded 0.2 .. 1.5 mm2 |
|
MPI-D enclosure – dimensions | ||
Enclosure type | Panel mount, nonflammable plastic material ‘Noryl’ | |
Dimensions (width x height x depth) | 144 mm x 72 mm x 130 mm | |
Enclosure depth with terminals | ca. 140 mm | |
Panel cut-out dimensions (width x height) | 138+1.0 mm X 68+0.7 mm | |
Panel maximum thickness | 5 mm | |
Weight | ca. 0.5 kg | |
Protection class from the front panel | IP54 | |
Protection class from the rear panel | IP30 | |
MPI-DN enclosure – dimensions | ||
Enclosure type | Wall mount, PC material | |
Dimensions (width x height x depth) | 257 mm X 217 mm X 125 mm (without cable glands)
257 mm X 247 mm X 125 mm (with cable glands) |
|
Weight | ca. 2.1 kg | |
Protection class | IP54 | |
Environmental conditions | ||
Ambient temperature | · MPI-D: 0 .. +50 °C
· MPI-DN: -20 .. +50 °C |
|
Relative humidity | 0 .. 75% (without steam condensation) | |
Storage temperature | -20 .. +80 °C | |
Overvoltage category | OV II | |
Pollution degree | PD 2 | |
LVD (safety) | EN 61010-1 | |
EMC | Directive 2014/30/EU:
· immunity for industrial environments according to EN 61326-1:2013 (Table 2) · conductive and radiated emissions Class A equipment according to EN 61326-1:2013 |
|
RoHS | Directive 2011/65/EU | |
Installation location | · MPI-D: Indoor only
· MPI-DN: Indoor or outdoor(2) |
|
(2)If additional protection against atmospheric precipitation is provided (roofing), the device can be installed outdoor. |